Applications

  • Capturing fine particles
  • Pre-filter for HEPA filters

Highlights

  • V-shaped design
  • Large filtration area
  • Simple and light weight
  • High dust holding capacity
  • Low initial pressure drop

Technical Specifications

Filter Standard:ISO 16890Max. Operating
Tempature:
80˚C
Filter Class:ISO ePM1 - ISO ePM2,5
- ISO ePM10
Model:V (Vertical),
H (Horizontal)
Media:High quality glass fiberSealing Compound:Two component
polyurethane
Frame:Aluminium,
Galvanised
& Stainless Steel
Seperators:Hotmelt
Rec. Final Pressure Drop
EN13053:
Initial ΔP +100 Pa or
initial ΔP x3
whichever is lower

Order Code

Filter TypeFilter ClassFrameDesignDimensions (mm)
FD : Duct Type
Fine Dust Filter
M6
F7
F8
F9
A: Aluminium
G: Galvanized Metal
SS: Stainless Steel 304
V: Vertical
H: Horizontal
202x600x87
202x600x65
Filter ModelEN 779
(cancelled)
ISO 16890Dimensions
WxHxD
(mm)
Filtration
Area
(m²)
Nominal
Airflow
(m³/h)
Initial
Pressure Drop
(Pa)
FD-M6-G-V-202-600-87M6ePM10 70%202x600x872,620050
FD-M6-G-H-600-202-65M6ePM10 70%600x202x652,620030
FD-F7-G-V-202-600-87F7ePM1 55%202x600x872,620065
FD-F7-G-H-600-202-65F7ePM1 55%600x202x652,620040
FD-F8-G-V-202-600-87F8ePM1 70%202x600x872,620090
FD-F8-G-H-600-202-65F8ePM1 70%600x202x652,620060
FD-F9-G-V-202-600-87F9ePM1 80%202x600x872,6200125
FD-F9-G-H-600-202-65F9ePM1 80%600x202x652,620090

“Differential Pressure Tolerance ( ±10% + 5 Pa ) or ( 10 Pa + 5 Pa ) whichever is greater”