To estimate filter-related electricity at constant airflow, multiply airflow by average filter pressure drop and operating hours, then divide by overall efficiency and 1,000. The result is in kWh when airflow is in m³/s, pressure in Pa and time in hours.
The important input is the average pressure drop during operation. A clean-filter value describes the start of the cycle. It does not describe the whole year.
Download the editable air-filter energy calculator. It includes two filter columns, visible calculation steps and an annual cost comparison. The starting numbers are an example, not current quotations or measured site savings.
The formula, with units attached
E = q × Δp̄ × t ÷ (1,000 × η)
| Symbol | Enter this | Unit |
|---|---|---|
| E | Calculated electricity associated with the filter's resistance | kWh |
| q | Airflow through the filter or selected bank | m³/s |
| Δp̄ | Time-average filter pressure drop | Pa |
| t | Operating time | hours |
| η | Overall efficiency from electrical input to useful air power | Decimal, for example 0.70 |
Scroll the table sideways to see all columns →
The formula is an engineering estimate for the stated duty. Eurovent 4/24 describes filter-energy evaluation under operating conditions and explains why those conditions matter. A standardised energy label answers a separate comparison question. Eurovent 4/24–2023, Update 1.
Pressure multiplied by volume flow gives air power in watts. Dividing by overall efficiency gives the corresponding electrical input in this model. Multiplying by hours gives Wh; dividing by 1,000 gives kWh.
Step 1: convert the airflow
Many filter data sheets give airflow in m³/h. Divide that number by 3,600 before using the formula:
3,400 m³/h ÷ 3,600 = 0.944444 m³/s.
Do not divide the hours by 3,600 as well. The formula already uses operating time in hours because the result is energy in kWh.
For a bank of parallel filters, decide whether the calculation covers one filter or the whole bank. If ten equal filters share the airflow, a one-filter calculation uses that filter's flow. A bank calculation uses the bank's total flow and the pressure drop across the bank. Do not use total bank flow and then multiply the answer by ten again.
Filter stages in series are different. The same air passes through each stage, and their pressure drops contribute to the total air path. Measure or model the relevant stages without double-counting them.
Step 2: choose a defensible average pressure
The spreadsheet assumes resistance rises linearly with operating time within each filter cycle. Under that assumption:
Average pressure drop = (initial pressure drop + final pressure drop) ÷ 2.
For 100 Pa at the start and 200 Pa at the end, the average is 150 Pa. The difference, 100 Pa, is the increase in resistance. It is not the average.
Use the midpoint only when that assumption is suitable for the purpose of the estimate. Real loading may accelerate or change after a dust event. Where measured records are available, use them to improve the calculation.
A laboratory curve against grams of test dust does not automatically become a curve against running hours. ISO 16890-3:2024 measures resistance as specified dust is captured; a site-time model needs a justified link to actual loading. ISO 16890-3:2024.
Step 3: enter the right efficiency
The η in this formula is not H13 efficiency, H14 efficiency or ePM1 efficiency. It describes the conversion of electrical input into useful air power.
The fan, motor and any drive losses need a consistent boundary. A motor efficiency of 90% does not mean the complete fan system converts 90% of its electrical input into useful air power. Use operating-point data or a clearly stated assumption.
Keep the same boundary when comparing candidates. If one calculation uses fan efficiency only and the other uses total electrical-to-air efficiency, their results are not directly comparable. The DOE fan-system guide is a useful reference for system power and operating-point assessment. DOE: Improving Fan System Performance.
Step 4: calculate energy, then cost
Using the spreadsheet's Filter A example:
E = 0.944444 × 150 × 6,000 ÷ (1,000 × 0.70) = 1,214.29 kWh/year.
At an assumed €0.283/kWh:
Electricity cost = 1,214.285714 × 0.283 = €343.64/year.
Keep unrounded values in the calculation and round the displayed result. Add the included filter-purchase and change costs separately.
The workbook opens with historical inputs from Ulpatek's July 2024 catalogue, page 68. Its energy figures have been recalculated with the explicit linear-rise assumption. The source candidates have different ePM1 values, 85% and 80%; both must meet the project's requirement before cost becomes the deciding factor. Ulpatek catalogue, page 68. The worked TCO article explains that comparison in full.
What the spreadsheet lets you change
Edit the amber input cells for airflow, hours, overall efficiency, tariff, starting and end-of-cycle pressure, annual purchases/changes, filter price and other cost per change.
Enter the planned number of changes yourself. The workbook does not predict service life from pressure drop or infer a replacement schedule. It assumes the stated average pressure represents the operating hours being assessed.
The results show filter-related electricity, electricity cost, filter/change cost and their total. Positive savings mean Filter A costs less within the included boundary.
Missing or invalid required inputs return “n.a.” in the affected results. For example, zero overall efficiency cannot produce a valid energy answer. Zero operating hours can produce zero energy while a separately entered filter purchase still has a cost.
Use one currency consistently. The workbook labels the example in EUR; change the labels as well as the numbers if your cost comparison uses another currency.
When you need a time-interval calculation
If airflow, resistance or efficiency changes substantially, split the operating record into intervals. Calculate the energy in each interval and add the results.
For example, assume these illustrative representative conditions:
| Interval | Airflow | Filter pressure drop | Hours | Overall efficiency | Energy |
|---|---|---|---|---|---|
| 1 | 1.0 m³/s | 100 Pa | 1,000 | 0.60 | 166.67 kWh |
| 2 | 0.5 m³/s | 80 Pa | 1,000 | 0.60 | 66.67 kWh |
| Total | 2,000 | 233.33 kWh |
Scroll the table sideways to see all columns →
Multiplying the separate average flow, 0.75 m³/s, by the separate average pressure, 90 Pa, gives 225 kWh. That differs because flow and pressure changed together. Finer intervals or suitable time-series data give a better estimate when the duty varies.
The supplied workbook is deliberately a simple constant-duty comparison. Do not force it to represent a changing operating history that needs this more detailed method.
What the answer does not include
The calculation covers the electrical contribution associated with the selected filter resistance. It does not include heating, cooling, all other AHU pressure losses or the whole building's energy use.
It also does not predict how a fixed-speed fan will respond to a different filter. A lower resistance can increase airflow rather than create the expected reduction in electrical input. Check controls and the fan curve before presenting a site saving.