Applications

  • Final filter for hygenic type AHU’s
  • Life science
  • Healthcare
  • Food & Beverages
  • Operating theatre LF units

Highlights

  • For high airflow rates (3000-4000 m³/h)
  • High quality glass fiber media
  • Guarented leak free
  • Tested and certified acc to EN 1822 – ISO 29463 for H13 – H14

Technical Specifications

Filter Standard:EN 1822 and ISO 29463Max. Operating Tempature:80°C -120°C
Filter Class:E10 - E11 - E12 - H13 - H14Gasket:EPDM, EPDM Flat continuous
and PU Foam
Media:High quality glass fibreDesign:U-Module
Frame:Galvanized, Stainless Steel, AluminiumSealing Compound: Two component polyurethane
Rec. Final Pressure Drop:Initial pressure drop x2,
(max. 600 Pa)
Seperator: Hotmelt

Order Code

Filter TypeFilter
Class
FrameCapacityDimensions
(mm)
Gasket
HHV : High Capacity
HEPA Filter with
V-Module Design
(Metal Frame)
E10
E11
E12
H13
H14
A: Aluminium
G: Galvanized Metal
SS: Stainless Steel 304
SS316: Stainless Steel 316
30: 3000 m3/h
40: 4000 m3/h
610x610x292P: Continuous Pu Foam
PP: Pu Foam on Both Side
E: EPDM Flat
EE: EPDM Flat on Both Side
C: Continuous Grey EPDM
CC: Grey EPDM on Both Side
Filter ModelEN 1822ISO 29463Dimensions
WxHxD
(mm)
Filtration
Area
(m²)
Pleat
Design
Nominal
Airflow
(m³/h)
Initial
Pressure Drop
(Pa)
HHV-H13-G-30-287-592-292-EH13ISO 35 H287x592x29211,9V-Module1370270
HHV-H13-G-30-305-610-292-EH13ISO 35 H305x610x29213V-Module1500270
HHV-H13-G-30-592-592-292-EH13ISO 35 H592x592x29224,5V-Module2830270
HHV-H13-G-30-610-610-292-EH13ISO 35 H610x610x29226V-Module3000270
HHV-H13-G-40-287-592-292-EH13ISO 35 H287x592x29216,9V-Module1880290
HHV-H13-G-40-305-610-292-EH13ISO 35 H305x610x29218,5V-Module2000290
HHV-H13-G-40-592-592-292-EH13ISO 35 H592x592x29234,8V-Module3760290
HHV-H13-G-40-610-610-292-EH13ISO 35 H610x610x29237V-Module4000290
HHV-H14-G-30-287-592-292-EH14ISO 45 H287x592x29213,7V-Module1415300
HHV-H14-G-30-305-610-292-EH14ISO 45 H305x610x29215V-Module1500300
HHV-H14-G-30-592-592-292-EH14ISO 45 H592x592x29228,2V-Module2830300
HHV-H14-G-30-610-610-292-EH14ISO 45 H610x610x29230V-Module3000300
HHV-H14-G-40-287-592-292-EH14ISO 45 H287x592x29218,3V-Module1880300
HHV-H14-G-40-305-610-292-EH14ISO 45 H305x610x29220V-Module2000300
HHV-H14-G-40-592-592-292-EH14ISO 45 H592x592x29237,7V-Module3760300
HHV-H14-G-40-610-610-292-EH14ISO 45 H610x610x29240V-Module4000300

“Differential Pressure Tolerance ±10%”