Applications

  • Shelter ventilation

Highlights

  •  For high airflow rates (3400 m³/h)
  • High quality glass fiber media
  • Guarented leak free
  • Tested and certified acc to EN 1822 – ISO 29463 for H13 – H14
  • Operating temperature up to 120°C

Technical Specifications

Filter Standard:EN 1822 and ISO 29463Max. Operating Tempature:120˚C
Filter Class: H13Gasket:Silicon
Media:High quality glass fiberDesign:V-Module
Frame:Galvanized, Stainless SteelSeperator: Hotmelt
Rec. Final Pressure Drop:Initial pressure drop x2,
(max. 600 Pa)

Order Code

Filter TypeFrameCapacityDimensions
(mm)
Gasket
NF : High Capacity
Nuclear Filter with
V-Module Design
G: Galvanized Metal
SS: Stainless Steel
34: 3.400 m3/h610x610x292W: Without
P: Continuous Pu Foam
PP: Pu Foam on Both Side
E: EPDM Flat
EE: EPDM Flat on Both Side
C: Continuous Grey EPDM
CC: Grey EPDM on Both Side
SS: Silicon on Both Sides
Filter ModelEN 1822ISO 29463Dimensions
WxHxD
(mm)
Filtration
Area
(m²)
Nominal
Airflow
(m³/h)
Initial
Pressure Drop
(Pa)
NF-G-34-287-592-292-CH13ISO 35 H287x592x29217,41600300
NF-G-34-305-610-292-CH13ISO 35 H305x610x29218,51700300
NF-G-34-592-592-292-CH13ISO 35 H592x592x29234,83200300
NF-G-34-610-610-292-CH13ISO 35 H610x610x292373400300

“Differential Pressure Tolerance ±10%”